506566−01 09/10
Page 24
Table 2. Adjustable Parameters Table (Installer)
Parameter Name
Installer
entry
NoteDependencyIncr.Max.Min.Default
Cooling Airflow Settings
High Cooling Airflow (CFM @
100% cool)
OU tons
(OUNC) *
400CFM
Min
CFM
Max
CFM
25 Outdoor Unit
present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Low Cooling Airflow (CFM @
lowest cool stage)
(See Note
1 below)
Min
CFM
Max
CFM
25 2+ stage
Outdoor Unit
present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Airflow Profile − Cooling DIP SW 0 3 1 Outdoor Unit
present
0–Text ID 0x0105
(A:ON:50%/30s,82% /
7.5min OFF:50%/30s)
1–Text ID 0x0106
(B:ON:82% / 7.5min;
OFF: No delays)
2–Text ID 0x0107 (C:ON:
No delays; OFF:
45sec delay)
3–Text ID 0x0108 (D:No
delays)
Heat Pump Airflow Settings
High Heat Pump Airflow
(CFM @ 100%)
OU tons
(OUNC) *
400CFM
Min
CFM
Max
CFM
25 Heat Pump
present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Low Heat Pump Airflow (CFM
@ lowest stage)
(See Note
2 below)
Min
CFM
Max
CFM
25 2+ stage Heat
Pump present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Other Parameters
Equipment Name Furnace N/A N/A N/A None Up to 35 characters
Continuous Indoor Blower
Airflow
DIP SW
(See Note
3 below)
Min
CFM
Max
CFM
25 None 1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Humidification Airflow Same as
above
Min
CFM
Max
CFM
25 Humidifier
present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Dehumidification Airflow
Percentage
140
(=70%)
120
(=60%)
160
(=80%)
2
(=1
%)
OU present
AND SC
algorithm
support
Percent of High Cooling
Airflow
Note 1: Minimum Outdoor Unit Cooling Stage as a percentage of High Cooling Airflow (value is rounded up to the closest number on
25 CFM resolution.
Note 2: Minimum Outdoor Unit Heating Stage as a percentage of High Heat Pump Airflow (value is rounded up to the closest number
on 25 CFM resolution).
Note 3: All communicating Installer Parameters default CFM values based on DIP switch setting (non−communicating value) are cal-
culated using the CFM conversion tables and rounded up to closest number on 25 CFM resolution.
Note 4: Parameter dependency − Certain parameters are dependent on others and may not be shown on the display.
Note 5: Default Values − Jumper/DIP switches impact the default value of some parameters.