Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
See
Chapter 4 Parts listing, Lenovo System x3550 M3 Type 4254 and 7944” on page 403 to determine which
components are customer replaceable units (CRU) and which components are field replaceable units (FRU).
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
Go to the IBM support website at
http://www.ibm.com/supportportal/ to check for technical information, hints,
tips, and new device drivers or to submit a request for information.
Error code
Description
Action
00580A1 Invalid DIMM population for mirroring mode Note: Each time you install or remove a DIMM, you
must disconnect the server from the power source;
then, wait 10 seconds before restarting the server.
1. If a fault LED is lit, resolve the failure.
2. Install the DIMMs in the correct sequence (see
“Installing a DIMM” on page 436).
00580A4 Memory population changed. Information only. Memory has been added, moved, or
changed.
00580A5 Mirror failover complete Information only. Memory redundancy has been lost.
Check the event log for uncorrected DIMM failure
events (see
“Event logs” on page 26).
00580A6
Spare memory channel activated Information only. Memory online-spare channel has
been activated to back up a failed DIMM. Check the
event log for uncorrected DIMM failure events.
0068002
CMOS battery cleared.
1. Reseat the battery.
2. Clear the CMOS memory (see
“System-board
switches and jumpers” on page 18
).
3. Replace the following components one at a time,
in the following order, restarting the server after
each one:
a. Battery
b. (Trained service technician only) System
board.
2011001
PCI-X SERR
1. Check the riser-card LEDs.
2. Reseat all affected adapters and riser cards.
3. Update the PCI adapter firmware.
4. Remove the adapter from the riser card.
5. Replace the following components one at a time,
in the order shown, restarting the server each
time:
a. Riser card
b. (Trained service technician only) System board
Chapter 3. Diagnostics 313