Electrical installation
Mains connection
5
91
EDK82MV752 DE/EN/FR 7.2
5 Electrical installation
5.1 Mains connection
Danger!
Dangerous electrical voltage
The discharge current to earth (PE) is > 3.5 mA AC or 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when touching the device in the event of an error.
Protective measures:
ƒ Implement the measures required in EN 61800−5−1. Especially:
– Fixed installation
– PE connection must comply with standards (PE conductor diameter
³ 10 mm
2
(Cu) or PE conductor must be connected twice)
8200mot409
35
5.1.1 Fuses and cable cross−sections
Type Mains
Installation acc. to EN 60204−1
FI
1)
Fuse Circuit breaker L1, L2, L3, PE
[mm
2
]
E82MV302_4B
E82MV402_4B
E82MV552_4B
E82MV752_4B
3/PE AC
320 ... 550 V;
45 ... 65 Hz
M16 A
M20 A
M25 A
M32 A
B16 A
B20 A
B25 A
B32 A
2.5
4.0
4.0
6.0
³ 300 mA
E82MV302_4B230
E82MV402_4B230
E82MV552_4B230
E82MV752_4B230
M16 A
M20 A
M25 A
M32 A
B16 A
B20 A
B25 A
B32 A
2.5
4.0
4.0
6.0
³ 30 mA
1)
Universal−current sensitive earth−leakage circuit breaker
Observe all national and regional regulations!