EasyManua.ls Logo

Lenze 8230 Series - Page 123

Lenze 8230 Series
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation and Software
118 BA8230
A-Output 2 terminal 35
This parameter determines which control variable is to be output as an analog value
at the monitor output (D/A output) terminal :35 (AA1). Digital resolution is 12 bit, the
range of values at the analog output is -10 V ... +10 V.
Privided that Scal. A-Output 2 = 100 % the following apply according to the selction
list:
- Output frequency f = rated frequency
(The rated frequency as supplied is 100 Hz.
At an output frequency of 50 Hz the output voltage is
5 V. In the negative direction also the output voltage
becomes negative).
- Speed Output:
frequency rated on Speed
Speed
V10 *
eg. 5 V: Synchronous speed at 50 Hz.
In the negative direction also the output voltage is
negative.
- Motor current Output 10 V, if the r.m.s. value of the fundamental wave of
the motor current is equal to the maximum maximum
controller current.
- Motor voltage Output 10 V, if the r.m.s. value of the fundamental wave of
the motor voltage is equal to the rated mains voltage
.
- Torque 10 V with rated torque of the parameterized motor.
- Motor power 10 V with rated power of the parameterized motor.
- Link voltage Output 10 V, if the link voltage is equal to the rectification
value of the rated mains voltage.
- Variable 2 = XIM 100 % magnetising current based on the rated current
of the unit.
As supplied: Motor current
Scaling A-Output 2
This parameter is used for scaling the D/A output at terminal :35. It represents the
reference value which produces a 10 V output.
Adjustment range: 0 ... 200 %
As supplied. 100 %
Show/Hide Bookmarks

Table of Contents

Related product manuals