Commissioning
BA8230 149
5.6.2 Ratings We will now enter the type data. This includes the mains voltage, the motor data and
the load mode.
Select the main menu option 06 = RATINGS on the control unit.
06=RATINGS
The type data includes the following parameters:
Rated inverter voltage
*)
Inverter kVA
*)
Mains voltage
Break type
Nom.Motor power
Nom.Motor voltage
Nom.Motor speed
Nom.Motor frequency
Type of circuit (Star/Delta)
Nom.Motor current
Cos Phi
Motor type
*)
Stall torque/Rated torque
Graduated number
Adjust mode
Adjust to 0
R-stator + R-cable
Fan Trigger
*)
Display only
The following parameters are to be set if they do not match the factory settings:
- Mains voltage with which the 8230 frequency inverter is to be operated.
- Break type The braking device permits electrical braking and
prevents an excessive rise in the link voltage. The braking
device takes effect at U
D
> 750 V.