Technical Data
58 BA8230
2.8 Dimensions,
Installation drawing, weights
2.8.1 8230 frequency inverter build-in units
Fig. 28: Dimensions, 8230 frequency inverter build-in units
The clearances above, below and to the side must be provided. The mains choke
may not be installed directly under the unit.
8230 frequency
inverter type
Frame size
Enclosure dimensions Weight Installation clearances
(Clearance for cooling air inlets)
Width B Depth T
1)
Height H top o bottom u at side s
[mm] [mm] [mm] [kg] [mm] [mm] [mm]
8231 8 495 419 1049 90 300 200 0
8232 8A 495 419 1225 90 300 200 0
8233 9 495 419 1499 140 300 200 0
8234 9A 495 419 1675 140 300 200 0
1)
The unit depth can be reduced by 19 mm by removing the decorative facia on the
door.
Table 18: Dimensions, weights, installation clearances