Technical Data
BA8230 57
Terminal :29/:30 ADDITIONAL DEMAND
Differential input, additional demand
As terminal :27/:28
Terminal :31 + 10 V/ 20 mA Supply voltage for
Terminal :32 - 10 V / 20 mA Demand channels (short-circuit
resistant)
Terminal :31 DC +10 V 20 mA voltage supply for demand channels
Terminal :32 DC -10 V 20 mA voltage supply for demand channels
Terminal :33 A-OUTPUT 1
Analog output for an analog value 0 ... ±10 V
Function adjustable (04 Analog I/O Terminal :33)
(Standard setting: Output frequency - see section 4.4.4)
Scaling adjustable through 04 Analog I/O - Scale analog output
Rating: 3 mA; load 3.3 k
D/A transformer: 12 bit accuracy, 0.3 % resolution
Terminal :34 0 V Reference potential for DC ±10 V
Terminal :35 A-OUTPUT 2
Analog output for an analog value 0 ... ±10 V
As analog output 1
(Standard setting: Motor current - see section 4.4.4)
Terminal :36 DC 0V A-OUTPUT
0 V for analog outputs A-OUTPUT 1 and A-OUTPUT 2
}
Show/Hide Bookmarks