BA8230 23
2.4.1.3 Line fuses for Installation instructions for a 3AC 8230 frequency inverter connection in the
operation class gL and customer’s low voltage distribution system:
cable cross-sections The NH fuses recommended for operation class gL and the cable cross-sections to be
used for 8230 frequency inverter 3AC mains connections are shown in the following
table. Minimum cross-sections for mains supplies cables with PVC insulation
according to EN 60204-1:1992 are given for an ambient temperature of ϑ = 40 °C and
laying method E.
8230 frequency inverter
type
Unit output current Recommended fuse
gL characteristics
Recommended cable
cross-sections for PVC
insulated copper cable
1.2 x Rated
current
1.5 x Rated
current
Max. current
for 60 s
Type 3-phase cables
NYY/ NYM
[A] [A] [A]
8231 257 216 324 315 A Gr.2 2x3x95 mm²
8232 304 257 365 355 A Gr.2 2x3x120 mm²
8233 396 325 488 400 A Gr.2 2x3x150 mm²
8234 483 400 600 500 A Gr.3 2x3x185 mm²
Table 10: 8230 frequency inverter AC line fuses
2.4.1.4 Fuse circuit breakers The above semiconductor fuses (aR-Characteristics) with 100 mm length to
DIN 43 653 can be installed as an alternative to fuse bases in conjunction with the
hand-operated fuse circuit breaker.
This creates a separation point in the 3AC mains supply and all poles of the
semiconductor fuses can be switched.
2.4.1.5 Mains contactor Contactors 3 AC 400 V, 50/60 Hz
On 3AC mains supplies which include (automatic) on/off switching of the mains
voltage at the 8230 frequency inverter input (eg. 8230 frequency inverter units with
optional brake chopper and braking resistor), 3-phase contactors according to the
following tables are used.
Important! Note the mains contactor control voltage!
8230 frequency
inverter type
Unit output current Contactors 3 AC
1.2 x Rated
current
1.5 x Rated
current
Max. current
for 60 s
Type
[A] [A] [A]
8231 257 216 324 LS247.22
8232 304 257 365
LS247.22
8233 396 325 488
CA-5-550A
8234 483 400 600
CA-5-550A
Table 11: Mains contactors
Mains contactors and accessories are stated for 400 V, 50/60 Hz mains voltage.