Technical Data
12 BA8230
Mechanical use prEN50178:1994/IPA90 DIN IEC86
(Vibration) T.2-6 10 ... 150 Hz
Electromagnetic
compatibility
3)
:
- Interference resistance To IEC1800-3 (IEC22G/21/CDV), EN50082-2,
suitable for use in an industrial environment
- Radiated interference To IEC1800-3 (IEC22G/21/CDV)
- industrial mains supply AC mains choke
4)
- public supply network Additional RFI filter
4)
EN50081-2, limit to EN55011 Group 1 Class A:
Mains choke and RFI filter
4)
EN50081-1, limit to EN55011 Group 1 Class B:
Mains choke, RFI filter and Motor filter
4)
1)
Adequate convection cooling must be provided for the 8230 frequency inverter control
electronics. No heat build up inside the 8230 frequency inverter.
2)
No salt spray mist.
3)
Connection to earthed network
4)
see section 3.7 for optional measures
Pulse frequency adjustable
- Standard 3 kHz
- Maximum Up to 6 kHz
For a chopping frequency of f
p
=6 kHz, a power reduction to 1.5 rated current is
required.
Servicing Data memory battery replacement required,
see section 7.1
Fan replacement recommended, see section 7.2
Check power connection screws, see section 7.3