Transport, Installation and Connection
BA8230 71
Note:
The cable cross-sections stated in Table 23 can only be considered general
guidelines. The cable dimensions must satisfy the regulations and any works
standards applicable at the installation.
8230 frequency inverter
Type
Mains connection Motor connection Screw connection
Motor + Mains connection
Recommended
copper cable
cross-sections
Applicable
overload
protection NH
fuse
Recommended
copper cable
cross-sections
Steel screw
Strength class 8.8,
not greased
Tightening
torque
Max. direct
single
connection
cross-section
at the unit
[mm²] [mm²] [Nm] [mm²]
8231 2 x 3 x 95 315 A 2 x 3 x 95 M12 92 200
8232 2 x 3 x 120 355 A 2 x 3 x 120 M12 92 200
8233 2 x 3 x 150 400 A 2 x 3 x 150 M12 92 200
8234 2 x 3 x 185 500 A 2 x 3 x 185 M12 92 200
Table 23:
Cable connections
Note concerning motor connection
The following main factors must be taken into consideration for connecting motors to
the 8230 frequency inverter:
8230 frequency inverter unit type: As standard the response threshold for earth
fault detection on the motor side is 10 % I
N
.
8230 frequency inverter pulse frequency
Motor insulation system: Details from the motor manufacturer concerning the max.
motor voltage/current in the motor terminal box, suitability for inverter operation
Cable type: Screened, with armouring or without screen
Effective cable length: Parallel cables, group supply
Cable cross-section: Voltage drop 1.75 % or 3 %
Suitable screened heavy current cable 0.6/1 kV
Cross-section [mm
2
]
Type Manufacturer
to 25 Ölfex-Servo - 730 CY Lappkabel
10 ... 120 Protoflex-EMV-CY
2YSLCY-J
Siemens
10 ... 185 NYCWY 3x XX/Y
(für Y jeweils größter Wert)
Normkabel