3 Short setup of the technology application
3.1 Preconditions
14
Lenze · 8400 "Position Sequencer" technology application · Software manual · DMS 1.0 EN · 07/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3 Short setup of the technology application
3.1 Preconditions
For the execution of the short setup described in the following, the setting of the most important
parameters (motor, feedback system, etc.) is assumed.
The "commissioning wizard 8400" serves to carry out a guided commissioning of the controller
based on the Lenze setting of the parameters.
How to proceed:
1. Before switching on:
Make sure that the inverter is inhibited (digital input terminal X5/RFR
open).
2. Switch on voltage supply of the controller.
For parameter setting and diagnostics of the controller without motor operation
, an external
24-V supply through a safely separated power supply unit (SELV/PELV) is sufficient.
3. Establish a communication link between controller and Engineering PC, e.g. via USB diagnostic
adapter (E94AZCUS):
• connect the USB diagnostic adapter to the X6 diagnostic interface.
• establish a connection between the USB diagnostic adapter and the PC via a free USB port.
4. Start »Engineer« on the Engineering PC, e.g. via the Windows® start menu:
Start All programs Lenze Engineering L-force Engineer...
After the program start, no project has been loaded first and the start-up wizard is displayed.
5. Create a new project or open a project already available.
6. Go to Project View and select the 8400 controller.
7. Click the icon to go online.
After a connection to the controller has been established, the following status is displayed in the
Status line:
8. Click the icon to start the commissioning wizard 8400.
• Now the commissioning wizard guides you step by step through the setting of the important
parameters for a quick commissioning.
•The Next button can only be activated again after all parameter settings in the device have
been reset via the Load Lenze setting button.
• Execute the commissioning wizard right to the end.
• You can skip the "Control mode" step by clicking Next (only relevant for "Speed actuating
drive" technology application).
You can find detailed information on the options of the start-up wizard and on the
general use of the »Engineer« in the online help for the program which you can call with
[F1].