Configuration
Code table
8
8.5
8.5−12
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0116
Selection list 2
Configuration of free digital
outputs (FDO)
l Signals can only be evaluated
when being networked with
automation interfaced
See System
Manual
(extension)
1 CFG: FDO−0 1000 FIXED0
... ... ... ...
32 CFG: FDO−31 1000 FIXED0
C0117
Selection list 2 Configuration of digital inputs
signals, function block DIGOUT
A change of the basic
configuration in C0005 changes
the signal assignment!
6.5−3
See System
Manual
(extension)
1 CFG: DIGOUT1 15000 DCTRL−TRIP Terminal X5/A1
2 CFG: DIGOUT2 10650 CMP1−OUT Terminal X5/A2
3 CFG: DIGOUT3 500 DCTRL−RDY Terminal X5/A3
4 CFG: DIGOUT4 5003 MCTRL−MMAX Terminal X5/A4
C0118
0 High active HIGH level is
active
Inversion of digital output signals,
function block DIGOUT
1 LOW active LOW level is active
1 DIGOUT1 pol 1 Terminal X5/A1
2 DIGOUT2 pol 1 Terminal X5/A2
3 DIGOUT3 pol 0 Terminal X5/A3
4 DIGOUT4 pol 0 Terminal X5/A4
C0120 OC6 LIMIT 0 00 {1 °C} 120 Threshold for I
2
× t monitoring
(motor).
l 0 = I
2
× t monitoring
switched−off
l I
2
× t > C0120 ð trip OC6
C0121 OH7 limit 150 45 {1 °C} 150 Setting of the operating
temperature for monitoring OH7
l Only for KTY at X8
l Monitoring OH7 is configured
in C0584
6.6−10
See System
Manual
(extension)
C0122 OH4 limit 80 45 {1 °C} 85 Configuration of monitoring OH4
l Monitoring of the heatsink
temperature
l Activating monitoring with
C0582
l Temperature in C0122 reached:
Warning OH4 is initiated
See System
Manual
(extension)
C0125 Baudrate 0
0 9600 baud
LECOM baud rate
l Baud rate for accessory module
2102
1 4800 baud
2 2400 baud
3 1200 baud
4 19200 baud
C0126 MONIT CE0 3
0 TRIP
Configuration of monitoring CE0
l Error message in case of
communication error AIF
See System
Manual
(extension)
2 Warning
3 Off
C0127 OC8 LIMIT 0 0 {1 °C} 120 Threshold for I
2
× t advance
warning (motor).
l 0 = I
2
× t advance warning
switched−off
l I
2
× t > C0127 ð fault message
OC8 (response set in C606)
C0128 TAU MOTOR 5.0 0.1 {0.1 min} 50.0 Thermal time constant of the
motor
The time constant is required for
calculating the I
2
× t
disconnection.