Configuration
Code table
8
8.5
8.5−54
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0860
Selection list 1 Configuration of analog input
signals, function block CAN−OUT
See System
Manual
(extension)
1 CFG: OUT1.W1 1000 FIXED0%
CAN−OUT1
2 CFG: OUT1.W2 1000 FIXED0%
3 CFG: OUT1.W3 1000 FIXED0%
4 CFG: OUT2.W1 1000 FIXED0%
5 CFG: OUT2.W2 1000 FIXED0%
CAN−OUT2
6 CFG: OUT2.W3 1000 FIXED0%
7 CFG: OUT2.W4 1000 FIXED0%
8 CFG: OUT3.W1 1000 FIXED0%
CAN−OUT3
9 CFG: OUT3.W2 1000 FIXED0%
10 CFG: OUT3.W3 1000 FIXED0%
11 CFG: OUT3.W4 1000 FIXED0%
C0861
Selection list 3 Configuration of input signals,
function block CAN−OUT
1 CFG: OUT1.D1 1000 FIXED0INC CAN−OUT1
2 CFG: OUT2.D1 1000 FIXED0INC CAN−OUT2
3 CFG: OUT3.D1 1000 FIXED0INC CAN−OUT3
C0863 0 FFFF Process input words, function
block CAN−IN
l Read only
l Bit 0 ... bit 15 (via byte 5 and
byte 6)
l Bit 16 ... bit 31 (via byte 7 and
byte 8)
See System
Manual
(extension)
1 DIS: IN1 dig0 CAN−IN1, bit 0 ... bit 15
2 DIS: IN1 dig16 CAN−IN1, bit 16 ... bit 31
3 DIS: IN2 dig0 CAN−IN2, bit 0 ... bit 15
4 DIS: IN2 dig16 CAN−IN2, bit 16 ... bit 31
5 DIS: IN3 dig0 CAN−IN3, bit 0 ... bit 15
6 DIS: IN3 dig16 CAN−IN3, bit 16 ... bit 31
C0864 Output of the signal type,
function block CAN−OUT
See System
Manual
(extension)
1 TYPEOUT1.W2 0 0 analog Analog signal CAN−OUTx.Wx (C0860) is output
to X4
2 TYPEOUT2.W1 0 1 digital 0−15 Digital signal
bit 0 ... bit 15
FDO−00 ... FDO−15 (LOW word,
C0116/1 ... C0116/15) are output
to X4
3 TypeOUT3.W1 0 2 low phase Low phase CAN−OUTx.D1 (LOW word, C0861)
is output to X4
C0865 Output of the signal type,
function block CAN−OUT
1 TYPEOUT1.W3 0 0 analog Analog signal CAN−OUTx.Wx (C0860) is output
to X4
2 TYPEOUT2.W2 0 1 digital 16−31 Digital signal
bit 16 ... bit 31
FDO−16 ... FDO−31 (HIGH word,
C0116/16 ... C0116/31) are output
to X1
3 TYPEOUT3.W2 0 2 high phase High phase CAN−OUTx.D1 (HIGH word, C0861)
is output to X4