Basic devices in the power range 250 ... 400 kW
Master and slave connection
5.5
5.5.2
5.5−5
EDSVF9383V EN 7.1−04/2012
Connection of the control cables between master and slave
DC+
DC-
0
2
1
1
0
4
0
5
1
3
9300VEC028
Fig. 5.5−4 Connection of the control cables between master and slave
1. Installation and connection of the ribbon cable :
By default the ribbon cable is inside the master. The plug is already
attached to the Drive Board.
Route the ribbon cable from the master to the Drive Board
connection in the slave, inserting the ribbon cable into the cable
ducts .
Plug the ribbon cable plug into the socket at the Drive Board.
2. Laying and connecting 2−core cables with plugs :
By default the cable is inside the master. The corresponding cable with
socket is in the slave.
Lay the two−core cable from the master to the socket in the slave.
Connect the 2−pole plug with the 2−pole socket in the slave.
3. Laying and connecting 10−core cables with plugs :
By default the cable is inside the master. The corresponding cable with
socket is in the slave.
Lay the two−core cable from the master to the socket in the slave.
Connect the 10−pole plug with the 10−pole socket in the slave.
How to connect the control
cables