EDS94TA10040xxxx EN 1.1 - 10/2008 L 61
9400 Technology applications | Synchronism with mark synchronisation
Parameter setting & configuration
Parameterisable function blocks
4.14.10 FollowErrorHysteresis
4.14.11 FollowErrorLimit
4.14.12 HomingSetPosition
Is an instance of Function
L_SdSetPosition Following error monitoring:
Conversion of the following error hysteresis selected in the real units of the machine
via C03916 into a position in [increments].
Parameter Possible settings Information
C03916 -214000.0000 unit 214000.0000 Position value
Initialisation: 0.0000 unit
C03917 String of digits Position unit
•Read only
C03918 -2147483647 2147483647 Status
•Read only
Is an instance of Function
L_SdSetPosition Following error monitoring:
Conversion of the following error limit select in the real units of the machine via
C03911 into a position in [increments].
Parameter Possible settings Information
C03911 -214000.0000 unit 214000.0000 Position value
Initialisation: 10.0000 unit
C03912 String of digits Position unit
•Read only
C03913 -2147483647 2147483647 Status
•Read only
Is an instance of Function
L_SdSetPosition Conversion of the home position selected in the real units of the machine via C03012
into a position in [increments].
"Homing" mode
(C 41)
Parameter Possible settings Information
C03012 -214000.0000 unit 214000.0000 Position value
Initialisation: 0.0000 unit
C03013 String of digits Position unit
•Read only
C03014 -2147483647 2147483647 Status
•Read only