Safety engineering
Appendix
Module error messages
1
133
EDS94AYAE EN 6.0
Error type/response/
Note
DescriptionField Error type/response/
Note
Description
Error number
PROFIsafe
64
0x40 F_Dest_Add does not equal F address
PROFIsafe parameter
setting/STO
No error status
65 0x41 F_Dest_Add = 0 or FFFFhex
66 0x42 F_Source_Add = 0 or FFFFhex
67 0x43 F_WD_Time is 0 msec
68 0x44 F_SIL exceeds technical SIL
69 0x45 F_CRC_Length error
70 0x46 F parameter version incorrect
71 0x47 PROFIsafe CRC1 error
72 0x48 reserved (PROFIsafe standard) −
73 0x49 reserved (PROFIsafe standard) −
74 0x4A reserved (PROFIsafe standard) −
Test functions
81 0x51 Error SD−Inx/CLx
(internal short circuit in one of the inputs)
Trouble/−
OFF state for all SD−In
82 0x52 Error SD−Inx/CLx
(internal short circuit in one of the inputs)
89 0x59 Short circuit SD−Out
93 0x5D Error − internal disconnecting path
(internal error of the safe switch−off logic)
Trouble/STO
OFF state for all SD−In and
SD−Out
94 0x5E Test pulse error − internal switch−off path
(internal error of the safe switch−off logic)
Trouble/STO