EasyManua.ls Logo

Lenze E84DGFCG Series - Motor Data Object (40; 0 X28)

Lenze E84DGFCG Series
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013 134
Implemented CIP™ objects
"AC Drive Profile" objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.3.1 Motor Data Object (40 / 0x28)
The "Motor Data Object" provides a data basis for motor parameters.
Class attributes
Instance attributes
Instance attributes for AC motor types
For a write access to the attributes RatedCurrent and RatedVoltage, the controller enable (RFR = 0)
has to be deactivated.
Supported service codes
Attribute
ID
Service Name Data type Value
1 Get Revision UINT 1 (0x0001)
2 Get Max. Instance UINT 1 (0x0001)
3 Get Number of Instances UINT 1 (0x0001)
Attribute
ID
Service Name Data type Value
1 Get NumAttr USINT Number of supported attributes
2 Get Attributes ARRAY of
USINT
Listing of the supported attributes
3 Get / Set MotorType USINT AC motor type
6: Wound-rotor induction motor
7: Squirrel-cage induction motor
Attribute
ID
Service Name Data type Value
6 Get / Set RatedCurrent UINT Rated stator current [100mA]
7 Get / Set RatedVoltage UINT Rated base voltage [V]
Service code
[hex]
Name Description
0x01 Get_Attributes_All Outputs a list of the attributes and the attribute's values for
a certain object.
0x0E Get_Attribute_Single Outputs the value of a certain attribute.
0x10 Set_Attribute_Single Changes the value of a certain attribute.

Table of Contents