Monitoring
77 Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10 Monitoring
Fault with regard to EtherNet/IP communication
The response of the Inverter Drive 8400 motec to a fault with regard to EtherNet/IP communication
can be set in the »Engineer« under the Monitoring tab.
Settings Description
Idle Mode The 32-bit real time header sent by the scanner is evaluated.
Run/idle flag (bit 0) = 1:
The scanner indicates the validity of the I/O data.
Run/idle flag (bit 0) = 0:
The I/O data are invalid and the response parameterised here (C13880/
1) is executed on the drive.
The I/O data are processed as set in (C13885
).
Overall Ethernet
Communication Timeout
If after the time set in (C13881
) there is no longer any access via the
»Engineer«, the response parameterised here is activated in the drive
(C13880/4
).
Fault Mode The adapter (Communication Unit) monitors the I/O connection to the
scanner.
If no "implicit message" has been received within the timeout time for
implicit messages parameterised by the scanner, the response
parameterised here (C13880/2
) is executed on the drive.
Overall Ethernet Timeout Time Here, the overall message timeout time (C13881
) is set.
If no message has been received within this time, the response
parameterised in (C13880/4
) is executed.
The following messages are monitored:
Implicit messages
Explicit messages
»Engineer« access via EtherNet/IP
Explicit Msg Timeout If no "explicit message" has been received within the timeout time for
explicit messages parameterised by the scanner, the response
parameterised here (C13880/3
) is executed on the drive.
Clear I/O Data (C13885
), serves to set the I/O data to be processed by the adapter to
maintain internal communication if ...
the CIP network status (C13862
) of the controlling I/O connection is not
"Connected" or
an idle event has occurred.