Electrical installaon
Operang Instrucons i510 protec10
6 Electricalinstallaon
6.1 Generaloverviewoftheconnecons
The connecon diagram is considered exemplary for all voltage and
power classes.
Deviang mains connecon diagrams can be found in the corresponding
chapters.
X216
Modbus RTU
X216
CANopen
NC
NO
COM
X9
"
GND
DO
DI
DI
DI
DI
DI
GND
AI
AI
GND
AO
X3
X105
+
"
M
+
J
J
X100
PE AC
PE
AC
PE
N
+
The following example shows the eecve wiring:
A Shield connecon for control
connecons
C
D
B
A
B Control cable
C EMC cable gland
D Low-capacitance motor cable
(C-core/core/C-core/shield
< 75/150 pF/m ≤ 2.5 mm² / ≥ AWG 14;
C-core/core/C-core/shield
< 150/300 pF/m ≥ 4 mm² / ≤ AWG 12)
E Power supply
6.2 EMC-compliantinstallaon
The drive system of inverter and drive meet the EMC Direcve
2014/30/EU if they are installed according to the guidelines of CE-typical
drive systems. These guidelines should also be followed in installaons
requiring FCC Part 15 or ICES 001 compliance.
The structure of the installaon place must support the EMC-compliant
installaon with shielded motor cables.
• Use suciently conducve shield connecons.
• Connect the housing with shielding eect to the grounded mounng
plate with a surface as large as possible, e.g. of inverters and
RFI lters.
• Use central earthing points.