Electrical installaon
Operang Instrucons i510 protec10
6 Electricalinstallaon
6.1 Generaloverviewoftheconnecons
The connecon diagram is considered exemplary for all voltage and
power classes.
Deviang mains connecon diagrams can be found in the corresponding
chapters.
X216
Modbus RTU
X216
CANopen
NC
NO
COM
X9
"
GND
DO
DI
DI
DI
DI
DI
GND
AI
AI
GND
AO
X3
X105
+
"
M
+
J
J
X100
PE AC
PE
AC
PE
N
+
The following example shows the eecve wiring:
A Shield connecon for control
connecons
C
D
E
B
A
B Control cable
C EMC cable gland
D Low-capacitance motor cable
(C-core/core/C-core/shield
< 75/150 pF/m ≤ 2.5 mm² / ≥ AWG 14;
C-core/core/C-core/shield
< 150/300 pF/m ≥ 4 mm² / ≤ AWG 12)
E Power supply
6.2 EMC-compliantinstallaon
The drive system of inverter and drive meet the EMC Direcve
2014/30/EU if they are installed according to the guidelines of CE-typical
drive systems. These guidelines should also be followed in installaons
requiring FCC Part 15 or ICES 001 compliance.
The structure of the installaon place must support the EMC-compliant
installaon with shielded motor cables.
Use suciently conducve shield connecons.
Connect the housing with shielding eect to the grounded mounng
plate with a surface as large as possible, e.g. of inverters and
RFI lters.
Use central earthing points.