Electrical installaon
Operang Instrucons i510 protec 11
6.3 Control terminals
Control terminals
Standard I/O
Input/output Terminal X3 Informaon
Digital inputs DI1, DI2, DI3,
DI4, DI5
DI3/DI4 can be oponally used as frequency or encoder input.
HIGH-acve/LOW-acve switchable
LOW = 0 ... +3 V,
HIGH = +12 V ... +30 V
Digital outputs DO1 Digital output (max. 100 mA for DO1 and 24-V output)
Analog inputs AI1, AI2 Can be oponally used as voltage input or current input.
Analog outputs AO1 Can be oponally used as voltage output or current output.
24-V input 24E Input for mains-independent power DC supply of control electronics
(including communicaon). Max. 1 A
10-V output 10 V Primarily for the supply of a potenometer (1 ... 10 kΩ).
Max. 10 mA
24-V output 24 V Primarily for the supply of digital inputs.
(Max. 100 mA for DO1 and 24-V output)
Reference potenal GND
Connecon system Pluggable
spring terminal
Rated power
hp 0.5 ... 7.5
kW 0.37 ... 5.5
Connecon X3
Connecon type Pluggable spring terminal
Max. cable cross-secon AWG 16
Stripping length inch 0.35
Tightening torque lb-in -
Tools required 0.4 x 2.5
6.4 Relay output
The relay is not suitable for direct switching of an electromechanical
holding brake.
Use a corresponding suppressor circuit in case of an inducve or
capacive load.
Rated power
hp 0.5 ... 7.5
kW 0.37 ... 5.5
Connecon Relay output X9
Connecon type Not pluggable
Max. cable cross-secon AWG 16
Stripping length inch 0.35
Tightening torque lb-in 1.8
Tools required 0.4 x 2.5
COM Common contact
NC Normally-closed contact
NO Normally-open contact
Max. switching voltage/
switching current
AC 240 V/3 A
DC 24 V/2 A
DC 240 V/0.16 A
Relay output
NC
NO
COM
X9
AC 240 V
3 A
6.5 CANopen, Modbus RTU
The network must be terminated with a 120 Ω resistor at the rst and last
physical node.
Set the „R“ DIP switch to ON at these network nodes.
Use the DIP switch to set the node address and baud rate and to acvate
the integrated bus terminang resistor.
Rated power
hp 0.5 ... 7.5
kW 0.37 ... 5.5
Connecon X216
Connecon type Not pluggable
Max. cable cross-secon AWG 16
Stripping length inch 0.35
Tightening torque lb-in -
Tools required 0.4 x 2.5
CANopen,
Modbus RTU