Technical data
Operang Instrucons i510 protec 7
3 Technical data
3.1 Standardsandoperangcondions
Conformies CE 2014/35/EU, 2014/30/EU, 2011/65/EU
EAC
TR CU 004/2011, TR CU 020/2011
Approvals
C
UL
US
UL 61800-5-1, CSA 22.2 No. 274
Energyeciency Class IE2 EN 50598-2
Degreeofprotecon IP20 EN 60529 For completely
and correctly
installed device.
NEMA 250 Type 1
UL 50
Power systems TT, TN Voltage from any phase to earth/ground
must not exceed 300 V.
Mains switching 3 x within one minute possible
Operaonwithresidualcurrent
circuit breaker
(120-V network and 230-V network)
Up to 7.5 hp 30 mA
Operaonwithresidualcurrent
circuit breaker
(400-V/480-V network)
Up to 7.5 hp 30 mA
Cable length without EMC category max. 109 yd (≤7.5 hp max. 54 yd)
Cable length for EMC Category C2 max. 21 yd (≤0.5 hp max. 16 yd)
Category C3 max. 38 yd (≤0.5 hp max. 16 yd)
Switching frequencies 2, 4, 8, 12, 16 kHz 2 or 4 kHz: above +45°C:
reduce rated output current by 2.5 %/°C
(I51AP222B at 4 kHz + 40°C)
8, 12 or 16 kHz: above +40°C:
reduce rated output current by 2.5 %/°C
Ambient temperature 131 °F (derang of 1.4 %/°F above 113 °F)
Max. output frequency 0 Hz ... 599 Hz
Overload capacity
(120-V/230-V network)
200 % for 3 s;
150 % for 60 s
Overload capacity
(400-V/480-V network)
200 % for 3 s