Electrical installaon
Operang Instrucons i510 protec16
6.10 3-phasemainsconnecon480V
Terminal data, 3-phase 480 V
Inverter I51APxxxF
Rated power
hp 1 ... 3 4 ... 7.5 1 ... 7.5 1 ... 3 4 ... 7.5
kW 0.75 ... 2.2 3 ... 5.5 0.75 ... 5.5 0.75 ... 2.2 3 ... 5.5
Connecon X100 PE X105
Connecon type Pluggable PE screw Pluggable
Max. cable cross-secon AWG 10 10 10 10 8
Stripping length in 0.3 0.3 0.4 0.3 0.3
Tightening torque lb-in 5.3 6.2 18 5.3 6.2
Tools required 0.5 x 3.0 0.6 x 3.5 T20 0.5 x 3.0 0.6 x 3.5
Fusing data
Rated power
hp 1 1.5 2 3 4 5 7.5
kW 0.75 1.1 1.5 2.2 3 4 5.5
Operaonwithoutmainschoke
Fuse
SCCR kA
5 5 5 5 5 5 5
Characteriscc
all acc. to UL 248/
Class CC, CF, J, T
all acc. to UL 248/
Class CF, J, T
Max. rated current A
30 30 30 30 63 63 63
Circuit breaker
SCCR kA
5 5 5 5 5 5 5
Characterisc
all acc. to UL 489
Max. rated current A
30 30 30 30 63 63 63
Earth-leakage circuit breaker
3-phase mains connecon ≥30 mA, type B
A residual current device (RCD) is oponal.
Mainsconnecon
3/PE
AC 340 V ... 528 V
45 Hz ... 65 Hz
F1
…
F3
Q1
X100
L1
L2/N
L3
PE
N
L3
L2
3/N/PE
AC 480 V
Motorconnecon
X105
+
"
M
+
J
J