Commissioning
Operang Instrucons i510 protec18
7.2.1 Funconsofthekeys
Key Actuaon Acon
Press briey • Navigaon in the menu
• Parameter alteraon
Press briey • Go to Menu/Parameters
• Conrm parameter
Press and hold for 3s • Save parameters
• “P. SAVED” in the display indicates that the parameters have been saved
Press briey Quit Menu/Parameters
Press briey Acvate keypad control
Press briey Start motor
Press briey Change rotang direcon
Press briey Stop motor
The motor must be at standsll before parameters can be changed or
conrmed.
The sengs are saved temporarily unl the motor is switched o again.
To save the sengs permanently, press and hold the key
for 3 s.
7.2.2 Example of keypad handling
Example for DO1 funcon assignment with parameter P420.02.
GROUP 4
P420.XX
P420.02
I/O setting
Fct. dig. outputs
DO1 funcon
7.2.3 Quick commissioning – terminal control
The following quick overview with graphical parameter representaon
is sucient for commissioning many applicaons with terminal control.
Further seng opons are described in this document or in the
commissioning document.
1. Load default seng = Set P700.01 to 1.
2. Set the following parameters for V/f characterisc control:
• Mains voltage P208.01
• V/f characterisc data: Base voltage P303.01
• V/f characterisc data: Base frequency P303.02
• Minimum frequency P210.00
• Maximum frequency P211.00
• Acceleraon me 1 P220.00
• Deceleraon me 1 P221.00
• Analog input 1: Min. frequency value P430.02
• Analog input 1: Max. frequency value P430.03
3. Press and hold the key
longer than 3 seconds in order to save the
sengs.
P211.00
P430.03
P430.02 P430.02
P220.00
P221.00
P210.00
I1
Frequency
With the wiring shown below, the inverter can be operated using the control
terminals (X3).
• Preset 1 is acvated if DI4 is connected.
• Preset 2 is acvated if DI5 is connected.
• Preset 3 is acvated if DI4 and DI5 are connected at the same me.