Commissioning
Operang Instrucons i510 protec18
7.2.1 Funconsofthekeys
Key Actuaon Acon
Press briey Navigaon in the menu
Parameter alteraon
Press briey Go to Menu/Parameters
Conrm parameter
Press and hold for 3s Save parameters
“P. SAVED” in the display indicates that the parameters have been saved
Press briey Quit Menu/Parameters
Press briey Acvate keypad control
Press briey Start motor
Press briey Change rotang direcon
Press briey Stop motor
The motor must be at standsll before parameters can be changed or
conrmed.
The sengs are saved temporarily unl the motor is switched o again.
To save the sengs permanently, press and hold the key
for 3 s.
7.2.2 Example of keypad handling
Example for DO1 funcon assignment with parameter P420.02.
GROUP 4
P420.XX
P420.02
I/O setting
Fct. dig. outputs
DO1 funcon
7.2.3 Quick commissioning – terminal control
The following quick overview with graphical parameter representaon
is sucient for commissioning many applicaons with terminal control.
Further seng opons are described in this document or in the
commissioning document.
1. Load default seng = Set P700.01 to 1.
2. Set the following parameters for V/f characterisc control:
Mains voltage P208.01
V/f characterisc data: Base voltage P303.01
V/f characterisc data: Base frequency P303.02
Minimum frequency P210.00
Maximum frequency P211.00
Acceleraon me 1 P220.00
Deceleraon me 1 P221.00
Analog input 1: Min. frequency value P430.02
Analog input 1: Max. frequency value P430.03
3. Press and hold the key
longer than 3 seconds in order to save the
sengs.
P211.00
P430.03
P430.02 P430.02
P220.00
P221.00
P210.00
A
I1
Time
Frequency
With the wiring shown below, the inverter can be operated using the control
terminals (X3).
Preset 1 is acvated if DI4 is connected.
Preset 2 is acvated if DI5 is connected.
Preset 3 is acvated if DI4 and DI5 are connected at the same me.