EasyManua.ls Logo

Lenze i510 protec Series

Lenze i510 protec Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installaon
Operang Instrucons i510 protec12
6.6 1-phasemainsconnecon120V
Terminal data, 1-phase 120 V
Inverter I51APxxxA
Rated power
hp 0.5 ... 1.5
kW 0.37 ... 1.1
Connecon X100 PE
X105
Connecon type Pluggable PE screw Pluggable
Max. cable cross-secon AWG 10 10 10
Stripping length inch 0.3 0.4 0.3
Tightening torque lb-in 5.3 18 5.3
Tools required 0.5 x 3.0 T20 0.5 x 3.0
Fusing data
Rated power
hp 0.5 1 1.5
kW 0.37 0.75 1.1
Operaonwithoutmainschoke
Fuse
SCCR kA 5 5 5
Characterisc all acc. to UL248/Class CC, CF, J, T
Max. rated current A 30 30 30
Circuit breaker
SCCR kA 5 5 5
Characterisc all acc. to UL 489
Max. rated current A 30 30 30
Earth-leakage circuit breaker
1-phase mains connecon ≥30 mA, type B
A residual current device (RCD) is oponal.
Mainsconnecon
PE
N
L3
L2
PE
N
L2
Motorconnecon
X105
+
"
M
+
J
J

Related product manuals