Electrical installaon
Operang Instrucons i510 protec12
6.6 1-phasemainsconnecon120V
Terminal data, 1-phase 120 V
Inverter I51APxxxA
Rated power
hp 0.5 ... 1.5
kW 0.37 ... 1.1
Connecon X100 PE
X105
Connecon type Pluggable PE screw Pluggable
Max. cable cross-secon AWG 10 10 10
Stripping length inch 0.3 0.4 0.3
Tightening torque lb-in 5.3 18 5.3
Tools required 0.5 x 3.0 T20 0.5 x 3.0
Fusing data
Rated power
hp 0.5 1 1.5
kW 0.37 0.75 1.1
Operaonwithoutmainschoke
Fuse
SCCR kA 5 5 5
Characterisc all acc. to UL248/Class CC, CF, J, T
Max. rated current A 30 30 30
Circuit breaker
SCCR kA 5 5 5
Characterisc all acc. to UL 489
Max. rated current A 30 30 30
Earth-leakage circuit breaker
1-phase mains connecon ≥30 mA, type B
A residual current device (RCD) is oponal.
Mainsconnecon
PE
N
L2
Motorconnecon
X105
+
"
M
+
J
J