Commissioning
Operang Instrucons i510 protec24
7.5.2 Group2:Basicseng
Display code Name Possiblesengs Keypad code Informaon
P225.00 Quick stop
deceleraon me
1.0 s Quick stop deceleraon me for “MS: Velocity mode”
• If the “Quick stop” funcon is acvated, the motor is brought to a standsll within the deceleraon me set here.
• The set deceleraon me refers to the period of deceleraon from the set maximum frequency (P211.00) to standsll. In the
case of a lower actual frequency, the actual deceleraon me is reduced accordingly.
Seng is not eecve in operang mode P301.00 = “CiA:Velocity mode”.
7.5.3 Group 3: Motor control
Display code Name Possiblesengs Keypad code Informaon
P320.04 Rated torque 50 ... 50000 rpm General motor data.
Congure sengs as specied by the data on the motor nameplate.
Note!
Take the phase connecon implemented for the motor (star or delta conguraon) into account when entering the motor
nameplate data. Only enter data associated with the relevant conguraon.
P320.05 Rated frequency
1.0 ... 1000.0 Hz
P320.06 Rated power 0.00 ... 655.35 kW
P320.07 Rated voltage 0 ... 65535 V
P320.08 Cosine phi 0.00 ... 1.00
P327.04 Idenfy motor data 0 ... 1 1 = start automac idencaon of the motor data.
• Inverter characteriscs, motor equivalent circuit data and controller sengs are idened and set automacally.
• The motor is energized during the procedure!
P327.05 Calibrate motor data
(non-energized)
0 ... 1 1 = start automac calibraon of the motor data.
• A default inverter characterisc is loaded.
• The motor equivalent circuit data and controller sengs are calculated on the basis of the currently set rated motor data.
• The motor is not energized.
7.5.4 Group7:Addionalfuncons
Display code Name Possiblesengs Keypad code Informaon
P700.01 Device commands:
Load default sengs
O/ready [0] Only status feedback
On / start [1] 1 = reset all parameters in the RAM memory of the inverter to the default seng that is stored in the inverter rmware.
• All parameter changes made by the user are lost during this process!
• This process may take some seconds. When the device command has been executed successfully, the value 0 is shown.
• Loading parameters has a direct eect on cyclic communicaon: The data exchange for control is interrupted and a
communicaon error is generated.
P700.03 Device commands:
Save user data
O/ready [0] Only status feedback
On / start [1] Execute device commands
In progress [2] Only status feedback
Acon cancelled [3]
No access [4]
No access
(inverter disabled)
[5]