Commissioning
Operang Instrucons i510 protec24
7.5.2 Group2:Basicseng
Display code Name Possiblesengs Keypad code Informaon
P225.00 Quick stop
deceleraon me
1.0 s Quick stop deceleraon me for “MS: Velocity mode”
If the “Quick stop” funcon is acvated, the motor is brought to a standsll within the deceleraon me set here.
The set deceleraon me refers to the period of deceleraon from the set maximum frequency (P211.00) to standsll. In the
case of a lower actual frequency, the actual deceleraon me is reduced accordingly.
Seng is not eecve in operang mode P301.00 = “CiA:Velocity mode”.
7.5.3 Group 3: Motor control
Display code Name Possiblesengs Keypad code Informaon
P320.04 Rated torque 50 ... 50000 rpm General motor data.
Congure sengs as specied by the data on the motor nameplate.
Note!
Take the phase connecon implemented for the motor (star or delta conguraon) into account when entering the motor
nameplate data. Only enter data associated with the relevant conguraon.
P320.05 Rated frequency
1.0 ... 1000.0 Hz
P320.06 Rated power 0.00 ... 655.35 kW
P320.07 Rated voltage 0 ... 65535 V
P320.08 Cosine phi 0.00 ... 1.00
P327.04 Idenfy motor data 0 ... 1 1 = start automac idencaon of the motor data.
Inverter characteriscs, motor equivalent circuit data and controller sengs are idened and set automacally.
The motor is energized during the procedure!
P327.05 Calibrate motor data
(non-energized)
0 ... 1 1 = start automac calibraon of the motor data.
A default inverter characterisc is loaded.
The motor equivalent circuit data and controller sengs are calculated on the basis of the currently set rated motor data.
The motor is not energized.
7.5.4 Group7:Addionalfuncons
Display code Name Possiblesengs Keypad code Informaon
P700.01 Device commands:
Load default sengs
O/ready [0] Only status feedback
On / start [1] 1 = reset all parameters in the RAM memory of the inverter to the default seng that is stored in the inverter rmware.
All parameter changes made by the user are lost during this process!
This process may take some seconds. When the device command has been executed successfully, the value 0 is shown.
Loading parameters has a direct eect on cyclic communicaon: The data exchange for control is interrupted and a
communicaon error is generated.
P700.03 Device commands:
Save user data
O/ready [0] Only status feedback
On / start [1] Execute device commands
In progress [2] Only status feedback
Acon cancelled [3]
No access [4]
No access
(inverter disabled)
[5]