Electrical installaon
Operang Instrucons i510 protec14
6.8 3-phasemainsconnecon230/240V
Terminal data, 3-phase 230/240 V
Inverter
I51APxxxC
I51APxxxD
Rated power
hp 0.5 ... 2 1.5 ... 3 0.5 ... 5.5 0.5 ... 2 3 ... 5.5
kW 0.37 ... 1.5 2.2 ... 4 0.37 ... 4 0.37 ... 1.5 2.2 ... 4
Connecon X100 PE X105
Connecon type Pluggable PE screw Pluggable
Max. cable cross-secon AWG 10 10 10 10 8
Stripping length in 0.3 0.3 0.4 0.3 0.3
Tightening torque lb-in 5.3 6.2 18 5.3 6.2
Tools required 0.5 x 3.0 0.6 x 3.5 T20 0.5 x 3.0 0.6 x 3.5
Fusing data
Rated power
hp 0.5 1 1.5 2 3 4 5
kW 0.37 0.75 1.1 1.5 2.2 3 4
Operaonwithoutmainschoke
Fuse
SCCR kA 5 5 5 5 5 5 5
Characterisc
all acc. to UL 248/Class CF, J, T
Max. rated current
A 40 40 40 40 40 80 80
Circuit breaker
SCCR kA 5 5 5 5 5 5 5
Characterisc all acc. to UL 489
Max. rated current A 30 30 30 30 30 80 80
Earth-leakage circuit breaker
3-phase mains connecon ≥30 mA, type B
A residual current device (RCD) is oponal.
Mainsconnecon
3/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
F1
…
F3
Q1
X100
L1
L2/N
PE
N
L3
L2
3/N/PE
AC 208 V ... 240 V
L3
Motorconnecon
X105
+
"
M
+
J
J