Electrical installaon
Operang Instrucons i510 protec 13
6.7 1-phasemainsconnecon230/240V
Terminal data, 1-phase 230/240 V
Inverter I51APxxxD
Rated power
hp 0.5 ... 2 3 0.5 ... 3 0.5 ... 2 3
kW 0.37 ... 1.5 2.2 0.37 ... 2.2 0.37 ... 1.5 2.2
Connecon X100 PE
X105
Connecon type Pluggable PE screw Pluggable
Max. cable cross-secon AWG 10 10 10 10
Stripping length inch
0.3 0.4 0.3
Tightening torque lb-in
5.3 6.2 18 5.3 6.2
Tools required
0.5 x 3.0 0.6 x 3.5 T20 0.5 x 3.0 0.6 x 3.5
Fusing data
Rated power
hp 0.5 1 1.5 2 3
kW 0.37 0.75 1.1 1.5 2.2
Operaonwithoutmainschoke
Fuse
SCCR kA 5 5 5 5 5
Characterisc all acc. to UL 248/Class CF, J, T
Max. rated current A 40 40 40 40 40
Circuit breaker
SCCR kA 5 5 5 5 5
Characterisc all acc. to UL 489
Max. rated current A 30 30 30 30 30
Earth-leakage circuit breaker
1-phase mains connecon ≥30 mA, type B
A residual current device (RCD) is oponal.
Mainsconnecon
1/N/PE
AC 170 V ... 264
V
45 Hz ... 65 Hz
F1
Q1
X100
L1
L2/N
PE
N
L3
L2
3/N/PE
AC 480 V
L3
2/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
F1
F2
Q1
X100
L1
L2/N
PE
N
L3
L2
3/N/PE
AC 208 V ... 240 V
L3
F1
F2
Q1
X100
L1
L2/N
2/PE
AC 170 V ...
264 V
45 Hz ... 65 Hz
PE
N
L2
2/N/PE
AC 208 V ...
240 V
Motorconnecon
X105
+
"
M
+
J
J