Error code Descripon Classicaon Remedy
Blocking
me[s]
Reset
possible
5180 24-V supply overload Warning • Check 24-V output and digital outputs for earth fault or overload. 0 Yes
6280 Trigger/funcons connected incorrectly Trouble Check and correct the assignment of the triggers to the funcons.
• When keypad or network control is acve, the two funcons “Inverter enable” (P400.01) and “Run”
(P400.02) can also be set to “Constant TRUE [1]” to start the motor.
0 Yes
7180 Motor overcurrent Error • Check motor load.
• Check drive dimensions.
• Adapt set warning threshold or error threshold to P353.01.
1 Yes
9080 Keypad removed Error • Plug in the keypad again or acvate another control source. 0 Yes
FF06 Motor overspeed Error • Adapt the maximum motor speed (P322.00) and the warning threshold or error threshold (P350.01). 1 Yes
FF37 Automac start disabled Error • Deacvate start command and reset error. 0 Yes
FF85 Keypad full control acve Warning
• Press the keypad key
to exit control mode.
0 Yes