9400 HighLine | Commissioning guide
Notes on special applications
Fan in sensorless operating modes
38 L EDB94AXX6954 DE/EN/FR/ES/IT 4.0
Adaptation of the current controller to a motor of a third-party manufacturer:
1. Enter motor nameplate data.
2. Optimise the switching performance of the inverter
3. Set motor parameters.
4. Optimise current controller (e.g. by means of the oscilloscope function in the
»Engineer«).
5. Activate flying restart mode.
Software manual 9400 HighLine:
• Chapter "Motor interface"
Sensorless vector control (SLVC)
Optimise control mode
Optimise current controller
or
• Chapter "Motor interface"
V/f control (VFCplus) or V/f closed loop control (VFCplus)
Optimise control mode
Optimise current controller