Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 94
12 Error messages
12.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Profibus watchdog: Monitoring time elapsed [0x01bc8130]
Profibus: Data_Exchange state exited [0x01bc8131]
Profibus watchdog: DP-V1 MSC2 monitoring time exceeded [0x01bc8132]
Response (Lenze setting printed in bold) Setting: C13880/1 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Permanent interruption of communication to the
PROFIBUS master.
Also see the chapter "Permanent interruption of
PROFIBUS communication" ( 81).
Check cables and terminals.
Response (Lenze setting printed in bold) Setting: C13880/1 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Data exchange via PROFIBUS has been stopped.
Also see the chapter "Permanent interruption of
PROFIBUS communication" ( 81).
Check cables and terminals.
The slave must receive new parameterisation and
configuration files from the master in order to be able to
exchange data again.
Response (Lenze setting printed in bold) Setting: C13880/2 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Permanent interruption of communication to C2-
PROFIBUS master.
Also see the chapter "Permanent interruption of
PROFIBUS communication" ( 81).
Check cables and terminals.