EasyManua.ls Logo

Liebert AC4 - Page 94

Liebert AC4
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setup Operation - Standby Testing
SETUP OPERATION
Select operation to edit
OPERATIONSTATE
1=AUTO SEQUENCINGOFF
2=STANDBY TESTINGOFF
3=FAILED STANDBYN
4=HOLD DELAY10:00
5=RESTART DELAY00:06
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:2
>STANDBY TESTING- N FOR ON, F FOR OFF
>[N]
>[N]
>COMMAND SUCCESSFUL
>EVERY ## DAYS
>[03] DAYS
>[
>COMMAND SUCCESSFUL
>AT
>[00:00]
>[
>COMMAND SUCCESSFUL
>FOR
>[10] MIN
>[
>COMMAND SUCCESSFUL
Failed Standby
For details on this feature, see Specify Failed Standby Response on page63.
Vertiv | Liebert® AC4 User Manual | 94

Table of Contents

Related product manuals