Specifications and Technical Data
55
Table 21 Maintenance Bypass Cabinet
kVA Type
I/P Voltage
(VAC)
Max Input
Current
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output
OCP CB Size (A)
030 A, J 208 104 125 208 83 125
030 B, K 480 47 60 208 83 125
030 B, K 600 37 50 208 83 125
030 B, K 220 101 125 208 83 125
030 C, L 480 48 60 480 36 50
030 C, L 600 38 50 600 29 40
030 C, L 220 105 125 220 79 100
030 D, M 480 47 60 208 83 125
030 D, M 600 38 50 208 83 125
030 D, M 208 108 150 208 83 125
030 D, M 220 103 125 208 83 125
030 E, N 480 48 60 480 36 50
030 E, N 600 39 50 600 29 40
030 E, N 220 106 125 220 79 100
020 A, J 208 69 90 208 56 70
020 B, K 480 31 40 208 56 70
020 B, K 600 25 30 208 56 70
020 B, K 220 68 90 208 56 70
020 C, L 480 32 40 480 24 30
020 C, L 600 26 40 600 19 30
020 C, L 220 70 90 220 52 70
020 D, M 480 31 40 208 56 70
020 D, M 600 25 40 208 56 70
020 D, M 208 72 90 208 56 70
020 D, M 220 68 90 208 56 70
020 E, N 480 32 40 480 24 30
020 E, N 600 26 40 600 19 30
020 E, N 220 70 90 220 52 70
015 A, J 208 52 70 208 42 60
015 B, K 480 23 30 208 42 60
015 B, K 600 19 30 208 42 60
015 B, K 220 51 70 208 42 60
015 C, L 480 24 30 480 18 30
015 C, L 600 19 30 600 14 20
015 C, L 220 52 70 220 39 50
015 D, M 480 23 30 208 42 60
015 D, M 600 19 30 208 42 60
015 D, M 208 54 70 208 42 60
015 D, M 220 51 70 208 42 60
015 E, N 480 24 30 480 18 30
015 E, N 600 19 30 600 14 20
015 E, N 220 53 70 220 39 50
010 A, J 208 35 50 208 28 40
010 B, K 480 16 20 208 28 40
010 B, K 600 12 15 208 28 40
010 B, K 220 34 50 208 28 40
010 C, L 480 16 20 480 12 15
010 C, L 600 13 20 600 10 15
010 C, L 220 35 50 220 26 40
010 D, M 480 16 20 208 28 40
010 D, M 600 13 15 208 28 40
010 D, M 208 36 50 208 28 40
010 D, M 220 34 50 208 28 40
010 E, N 480 16 20 480 12 15
010 E, N 600 13 20 600 10 15
010 E, N 220 35 50 220 26 40