6. Autostart Operation
6.4 Behavior
The following links to videos show how to set up the panel for sample applications:
Click here to view Dual Float Empty.
Click here to view Transducer with Backup Switches.
6.4.1 Configuring Operation
Configuring Autostart begins with selecting the desired behavior. The two choices are:
1. High to low, examples:
• High water level to low water level
• High pressure to low pressure
• High temperature to low temperature
2. Low to high, examples:
• Low water level to high water level
• Low pressure to high pressure
• Low temperature to high temperature
6.4.2 Configuring Start and Stop Events
The next step is to define the start and stop events. The choices are:
• Single switch
• Cycle Run
– Start upon entering Autostart modes
– Stops after x minutes
– Restarts after y minutes
• Pressure Washer
– Manually started and stopped
– Switched input toggles between idle and Intermediate RPM
• Remote Control
– Start and stop via switch
– Throttle up and down via two other switches
– Single start/stop
• Dual switch
– Start and stop via dual (high and low) switches
• Transducer