Chapter 3 Installation and Wiring
XBC E-Type Main Unit 3-7 Ver. 1
Example calculation:
Item
Model Number
Current
Supply Current
CPU
XBC-DN20E
600mA
Current Draw
Slot 0 Module
XBO-DC04A
80mA
Slot 1 Module
XBO-DA02A
150mA
Totals
Current Required
230mA
Current Remaining
370mA
1) Internal Current Consumption (DC 5V)
Type Model
Consumption current (Unit : )
Option module
XBO-DC04A
80
XBO-TN04A
100
XBO-AD02A
50
XBO-DA02A
150
XBO-AH02A
150
XBO-RD01A
30
XBO-TC02A
50
XBO-RTCA
30
XBO-M2MB
-

Table of Contents