EasyManua.ls Logo

LS Industrial Systems XBC-DR10E - Chapter 4 CPU Specifications

LS Industrial Systems XBC-DR10E
542 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 CPU Specifications
XBC E-Type Main Unit 4-1 Ver. 1
Chapter 4 CPU Specifications
4.1 General Specifications
No. Items Specification Reference
1
Ambient Temp.
0 ~ 55
°
C
-
2 Storage Temp. 25 ~ +70 °C
3 Ambient humidity 5 ~ 95%RH (Non-condensing)
4
Storage humidity
5 ~ 95%RH (Non-condensing)
5
Vibration
resistance
Occasional vibration
-
Frequency
Acceleration
Amplitude
Times
IEC61131-2
10
f
<
57Hz
0.075mm
10 times
each
direction
(X,Y and Z)
57
f
150Hz
9.8m/s
2
(1G)
Continuous vibration
Frequency
Acceleration
Amplitude
10
f
<
57Hz
0.035mm
57
f
150Hz
4.9m/s
2
(0.5G)
6 Shock resistance
Peak acceleration : 147 m/s
2
(15G)
Duration : 11ms
Half-sine, 3 times each direction per each axis
7 Noise resistance
Square wave
impulse noise
AC: ±1,500 V
DC:
±
900 V
LSIS standard
Electrostatic
discharge
Voltage: 4kV (Contact discharge)
IEC61131-2
IEC61000-4-2
Radiated
electromagnetic
field noise
80 ~ 1,000 MHz, 10V/m
IEC61131-2,
IEC61000-4-3
Fast transient
/Burst noise
Segment
Power supply
module
Digital/Analog Input/Output,
Communication Interface
IEC61131-2
IEC61000-4-4
Voltage
2kV
1kV
8
Environment
Free from corrosive gases and excessive dust
-
9 Altitude Up to 2,000 ms
10 Pollution degree 2 or less
11
Cooling
Air-cooling
1. 1) IEC (International Electrotechnical Commission): An international nongovernmental organization which
promotes internationally cooperated standardization in electric/electronic field, publishes international
standards and manages applicable estimation system related with.
2. 2) Pollution degree: An index indicating pollution degree of the operating environment which decides
insulation performance of the devices. For instance, Pollution degree 2 indicates the state generally that only
non-conductive pollution occurs. However, this state contains temporary conduction due to moisture.
Notes

Table of Contents

Related product manuals