Chapter 3 Connection Configuration
XBC E-Type Main Unit 3-41 Ver. 1
Item
Comm. Port 1 Specifications
Comm. Port 2 Specifications
Serial communication method RS-232C RS-232C/RS-485 Selectable
Modem connection function N/A N/A
Data type
Data bit 8 7 or 8
Stop bit 1 1 or 2
Parity None (fixed) Even/Odd/None
Synchronization type Asynchronous type Asynchronous type
Transmission speed (bps) 115200 bps (fixed)
1200/2400/4800/9600/19200/
38400/57600/115200 bps available
Station No. setting 0 (fixed)
Setting range: 0-255,
Max. station
No. available: 32 stations
Transmission distance
Max. 50ft (15m) Max. 50ft/1640ft (15m/500m)
Diagnosis function
Check available by XG-PD
diagnosis service
Check available by XG-PD
diagnosis service
3.8.3 Comm. Port 1 Connection
1. Comm. Port 1 can be used for communication between PLC and devices that support LSIS
CPU protocol using RS232C.