Chapter 4 RTD Input Module (XBF-RD04A, XBF-RD01A)
4.8 Scaling Function
It is used to scale and output the range specified by the user other than temperature range.
Scaling expression =
2
)200010( +×eTemperatur
Ex.) When scaling is allowed and sensor input is 200 with PT100 sensor, scaling value is as follows.
Scaling value =
2
)200010200( +×
= 2000
The figure below displays the relation between temperature input and scaling value.
0.0
-
200.0
Temperature
Conversion value
Scaling
conversion
v
alue
600.0
4000
2000
200.0
4 - 7