XGB Analog edition manual
2 - 40
2.14 Troubleshooting
2.14.1 RUN LED flickers
Error code
(Dec.)
Error Details Action
50#
Filter constant setting
range exceeded
Change filter constant setting value within 1 ~ 99.
60#
Time average setting
range exceeded
Change time average setting value within 4 ~
16000.
70#
Frequency average
setting range exceeded
Change frequency average setting value within 2
~ 64000.
# indicates channel number.
RUN LED f
lickers
.
RUN LED f
lickers
0.2s intervals.
It seems to be a module defect.
Contact the nearest agency or LS branch office.
RUN LED f
lickers
1s intervals.
It is Run parameters setting error. Check the error code to
take action against as follows in the table below.