Chapter 5 Thermocouple Input Module (XBF-TC04S,TC04B)
5.8.4 Error code and measure
(1) Measure when error flag of data I/O area (U device) occurs.
Device
assignment
(‘S’, ‘H’ type)
Device
assignment
(IEC type)
Description Content Measure
U0x.00.0 %UX0.x.0
CH0 offset/gain adjustment
error
On: error
Off: normal
If repeated when restarting
the power, contact custom
service center
U0x.00.1 %UX0.x.1
CH1 offset/gain adjustment
error
U0x.00.2 %UX0.x.2
CH2 offset/gain adjustment
error
U0x.00.3 %UX0.x.3
CH3 offset/gain adjustment
error
U0x.00.D %UX0.x.13 Module offset/gain backup error
If repeated when restarting
the power, contact custom
service center
U0x.00.E %UX0.x.14 Module H/W error
If repeated when restarting
the power, contact custom
service center
U0x.01.8
%UX0.x.24
CH0 setting error
Parameter setting
On: setting error
Off: setting
normal
Check the parameter setting
area (address 27~30) by GET
instruction, solve the setting
error contents.
U0x.01.9
%UX0.x.25
CH1 setting error
U0x.01.A
%UX0.x.26
CH2 setting error
U0x.01.B
%UX0.x.27
CH3 setting error
(2) Checking error information area (address 27~30) of operation parameter area
(a) Setting error information area (address 27~30)
Bit Description
Related memory
address
Hex.
Dec.
Bit0
Sensor type setting (Off: normal, On: error)
01
H
~04
H
1~4
Bit1
Filter constant setting (Off: normal, On: error)
06
H
~09
H
6~9
Bit2
Average processing method setting
(Off: normal, On: error)
0A
H
~0D
H
10~13
Bit3
Time average value (Off: normal, On: error)
0E
H
~11
H
14~17
Bit4
Count average value (Off: normal, On: error)
Bit5
Moving average value (Off: normal, On: error)
Bit6
Scaling range (Off: normal, On: error)
13
H
~1A
H
19~26
(b) Checking setting error information
Check the setting error information (address 27~30) area by GET instruction.