EasyManua.ls Logo

Lucent Technologies KS-20472 - Installation; Tools and Equipment

Lucent Technologies KS-20472
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lucent Technologies Round Cell Batteries
Issue 3 December 1999 Installation 6 - 1
6 Installation
Introduction
In This Section This section describes the procedures for installing the Round Cell
batteries. Please read the safety statements and precautions in
Section 4 before unpacking and installing the batteries.
Installation Tools,
Materials, and Test
Equipment
Use the following tools, materials, and test equipment for installing and
testing the Round Cells:
• Protective clothing and equipment:
– rubber gloves, apron, and overshoes
– impact-resistant, splash-proof goggles or full-face mask
– safety hard hat
• Hoist and battery lifting clamp
• Gantry extension (required for 3-tier arrangements)
• Flashlight with plastic or rubber housing
• Cleaning cloth
• Soda (sodium bicarbonate or sal soda) and/or lime to neutralize
spilled electrolyte
• Eyewash kit (KS-21527, L3)
• Eyewash solution (KS-21527, L4)
• Insulated torque wrench capable of measuring 150 inch-pounds
• Insulated 1/2-inch box wrench
• 3-inch and 6-inch wrench extensions
• Hydrometer (range 1.150 to 1.240) (KS-5499 List 1306)
• Thermometer (KS-5499 List 1352, List 1353)
• Sandpaper
• Small, stiff brush
• DMM (Digital Multimeter) with an accuracy of 0.02 percent on the
dc scale
• A dc power source capable of supplying 2.55 volts per cell and a
current capability of at least 10 amperes

Table of Contents