Issue 3 December 1999 Operation and Maintenance 7 - 3
Check and Record Battery Float Voltage
Interval Perform this procedure monthly.
Guidelines The float voltage can be read four ways:
at the charger
at the battery monitor
with a volt/ohm meter at the battery disconnect
at the battery terminals
Check meter accuracy and calibration periodically.
Caution
Use extreme caution when making voltage readings to prevent
accidental grounding or shorting of leads during test operations.
Connections at the meter should be secure and free of any
possibility of touching or becoming grounded.
Never remove connections at the meter end without first
disconnecting the test leads from the battery. Remove test lead
connections at the battery immediately after each reading is taken.