Lucent Technologies Round Cell Batteries
6 - 22 Installation Issue 3 December 1999
Electrolyte Levels
Adjustments Do not adjust electrolyte levels until the cells have been on continuous
float charge for at least two weeks. If levels are low (more than 1/4-inch
below the low-level mark) after this time, add nominal specific gravity
sulfuric acid which meets the requirements of Federal Specification
0-S-801B. If levels are less than 1/4-inch below the low-level mark, add
approved water. If the electrolyte levels are higher than 1/4-inch above
the top level line, at normal room temperature, adjust by removing
electrolyte. Once the electrolyte has been properly adjusted, make all
further adjustments by adding approved water only.
Note: Use only distilled or deionized water for storage battery use to
bring electrolyte up to the required level.