Lucent Technologies Round Cell Batteries
7 - 10 Operation and Maintenance Issue 3 December 1999
Inspect Battery Jars and Stands
Interval Perform these procedures annually.
Cleaning Cell Jars
and Covers
Cleaning Cell Jars and Covers
Step Action
1
Depending on whether or not spilled electrolyte is on the cells,
clean using one of the following methods:
If electrolyte has dripped on cells, neutralize the electrolyte
by wiping it up with a weak soda solution.
If there is no spilled electrolyte on the cells, but general
cleaning is needed, clean with a cloth dampened in clean
water.
2
Properly dispose of cleaning cloths.
Note: Electrolyte is considered to be Hazardous Waste. After
cleaning corroded areas, dispose of cleaning cloths according
to local, state, and federal regulations.