Lucent Technologies Round Cell Batteries
8 - 2 Discharge and Power Data Issue 3 December 1999
Table 8-A: Ratings Table for List 1S Round Cell Batteries
(Discharge Currents are in Amperes)
Hours
Reserve At
77°F*
End Of Discharge Volts Per Cell
1.75 V 1.80 V 1.84 V 1.86 V 1.88 V 1.90 V
1.0 650 600 545 485 440 400
1.5 545 500 450 400 383 343
2.0 460 440 400 373 341 311
2.5 400 387 354 329 306 286
3.0 360 347 319 301 280 259
3.5 333 313 291 277 260 241
4.0 304 287 268 256 242 226
4.5 281 266 250 240 227 212
5.0 260 247 235 226 213 198
5.5 244 233 222 214 203 189
6.0 231 220 210 204 193 180
7.0 206 198 191 186 177 167
8.0 188 181 176 172 163 154
9.0 173 166 164 160 152 143
10.0 161 154 153 151 143 135
Note: The values in this table include intercell connector loss. This loss is based on the
use of four 12" x 1" x 1/8" lead-plated copper straps with an average intercell resistance of
31 microohms.
*Hours reserve reflect cell performance at electrolyte specific gravity of 1.215 ±0.005 at
77°F.