Lucent Technologies Round Cell Batteries
6 - 4 Installation Issue 3 December 1999
Unpacking and Handling, continued
Cleaning Jars If the jar is dirty when removed from the shipping container, clean the
jar with a cloth dampened in clean water before installing in the rack.
Cleaning Posts Round Cells are shipped with the posts coated with NO-OX-ID A
®
(regular or special) compound. If the posts have come in contact with
acid due to electrolyte spillage, clean them as follows:
Note
Use only water to clean jars.
Cleaning Posts
Step Action
1
Remove the NO-OX-ID A
®
(regular or special) compound by
wiping with a dry cloth.
2
Neutralize the posts with a weak soda solution.
3
Wipe the neutralized surfaces with a cloth dampened in clean
water.
4
Recoat the posts and all other exposed lead surfaces, including
the round shoulder below the square post, with NO-OX-ID A
®
(regular or special) compound.