ND30PNET-09 - User's Manual
30
7.7 Modbus
We choose Modbus group in the options and confirm with
Select
.
Fig.21. Screens of Modbus group
Table 10
No.
Parameter name
Characteristic / value
Description
Default
value
1
Address
1…247
Address on the Modbus
network.
1
2
Baud rate
4800 b/s, 9600 b/s,
19,2 kb/s, 38,4 kb/s,
57,7 kb/s, 115,2 kb/s
Baud rate
9600 b/s
3
Mode
RTU 8N2, RTU 8N1,
RTU 8O1, RTU 8N1
Transmission mode
RTU 8N2
4
Default settings of registers
42xx
No, Yes
Programmable read-only
register group
No