ND30PNET-09 - User's Manual
32
8 SERIAL INTERFACES
8.1 RS485 INTERFACE – the list of parameters
The implemented protocol is in accordance with the PI-MBUS-300 Rev G standard of Modicon
Company. The list of serial link parameters of ND30PNET meter:
ID 0xE0,
meter address 1..247,
baud rate 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kbit/s,
operation mode Modbus RTU,
information unit 8N2, 8E1, 8O1, 8N1,
maximum time to commence the response 600 ms,
maximum number of read registers in one query
- 61 registers – 4 byte,
- 122 registers – 2 byte,
implemented functions -03, 04, 06, 16, 17,
- 03, 04 registers reading,
- 06 saving one register,
- 16 saving n - registers,
- 17 identification of the device,
Default settings: address 1, baud rate 9.6 kbit/s, mode RTU 8N2.
8.2 Examples of registers reading and saving
Readout of n-registers (code 03h)
Example 1 . Readout of 2 registers 16-bytes of integer type, starting with the register addressed
0FA0h (4000) - registers values 10, 100.
Request: