ND30PNET-09 - User's Manual
33
Request:
Address of
the device
Function
Address of the register
Number of registers
Checksum
CRC
B1
B0
B1
B0
01
03
1B
58
00
04
C3 3E
Response:
Address
of the
device
Function
Number
of bytes
Value from
register 1B58
(7000)
Value from
register 1B59
(7001)
Value from
register 1B5A
(7002)
Value from
register 1B5B
(7003)
Checksum
CRC
B3
B2
B1
B0
B3
B2
B1
B0
01
03
08
41
20
00
00
42
C8
00
00
E4 6F
Example 3 . Readout of 2 registers 32-byte of float type as a combination of 2 registers 16-byte
starting with the register addressed 1770h (6000) - registers values 10, 100.
Request:
Address of
the device
Function
Address of the register
Number of registers
Checksum
CRC
B1
B0
B1
B0
01
03
17
70
00
04
4066
Response:
Address of
the device
Function
Number
of bytes
Value from
register
1770h(6000)
Value from
register
1770h(6000)
Value from
register
1772h(6002)
Value from
register
1772h(6002)
Checksum
CRC
B1
B0
B3
B2
B1
B0
B3
B2
01
03
08
00
00
41
20
00
00
42
C8
E4 6F
Example 4 . Readout of 2 registers 32-byte float type, starting with the register addressed
1D4Ch (7500)
- registers values 10, 100.
Request:
Address of
the device
Function
Address of the register
Number of registers
Checksum CRC
B1
B0
B1
B0
01
03
1D
4C
00
02
03 B0

Other manuals for Lumel ND30PNET

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lumel ND30PNET and is the answer not in the manual?

Lumel ND30PNET Specifications

General IconGeneral
BrandLumel
ModelND30PNET
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals