a#lt
Memory of alarm 2
off
off: disabled
on: enabled
a$sp
Set point value for absolu-
te alarm 3
100.0
o
C MIN...MAX 3)
a$du
Deviation from the set
point value for relative
alarm 3
2.0
o
C
-200.0... 200.0
o
C
(-360.0... 360.0
o
F)
a$Hy
Hysteresis for alarm 3 1.0
o
C
0.2...100.0
o
C
(0.2...180.0
o
F)
a$lt
Memory of alarm 3
off
off: disabled
on: enabled
hBsp
Set point for the heater
damage alarm
0,0 A 0.0...50.0 A
hBHy
Hysteresis for the heater
damage alarm
0.1 A 0.1...50.0 A
oSsp
Set point for the control-
ling element damage
alarm (short-circuit)
0.0 A 0.0...50.0 A
oSHy
Hysteresis for the con-
trolling element damage
alarm (short-circuit)
0.1 A 0.1...50.0 A
spp – Set point value parameters
sPmd
Kind of set point value sp1.2 sp1.2: set point value SP1
or SP2
Rmin: set point value with
soft start in units
per minute
RHr: set point value with soft
start in units per hour
in2: set point value from the
additional input
prg: set point value from
programming control
/prg
Program No to carry out 1 1...15