13.2. Defi nition of Set Point Value Programs.
One can defi ne 15 programs. The maximum number of seg-
ments in the program is equal to 15.
To render visible parameters related to the programming
control in the menu, the parameter sPmd must be set on prg.
For each program, one must set parameters given in the submenu
of program parameters. For each segment, one must select the kind
of segment and next, parameters depending on the kind of segment,
acc. to the table 6. One must also set the output state (only when
out1...out3 are set on eu1, eu2) – parameter eu1 and eu2.
List of segment confi guration parameters Table 6
type = time type = rate type = duel
type = end
Tsp Tsp time
time rr
hldu hldu
The g. 26 and the table 7 represent an example of set point value
program. It is assumed in the program that the temperature in the object
has to increase from the initial temperature in the object up to 800ºC,
with the rate of 20ºC per minute, at the active locking from the deviation.
Next, during 120 minutes, the temperature is maintained (locking disab-
led), after that, the temperature has to decrease to 50ºC during 100
minutes (locking disabled). During the object cooling, one must turn
on the fan connected to the auxiliary output no 2 (parameter out2
set on eu1).